Ventilation Requirement Calculator

Calculate required ventilation airflow based on room area, occupancy, and ASHRAE standards. Free tool for HVAC engineers and designers.

The Ventilation Requirement Calculator determines the minimum outdoor air ventilation rate required for different space types based on ASHRAE 62.1 standards. Calculate CFM requirements from occupancy density and floor area to ensure healthy indoor air quality.
Input Parameters
Custom Ventilation Rates
ASHRAE 62.1 Formula

Vot = Rp × Pz + Ra × Az

Vot = Total outdoor air (CFM)Rp = CFM per personPz = Zone populationRa = CFM per ft²Az = Zone area (ft²)
Calculations based on ASHRAE 62.1-2019 Ventilation for Acceptable Indoor Air Quality. These are minimum requirements - actual design may need higher rates.

What is Ventilation Requirement?

Ventilation requirement is the minimum amount of outdoor (fresh) air that must be supplied to an occupied space to maintain acceptable indoor air quality. ASHRAE Standard 62.1 specifies minimum ventilation rates based on two components: a people-based component (Rp) that varies with occupancy, and an area-based component (Ra) that accounts for off-gassing from materials, furnishings, and building surfaces. Total required ventilation = (Rp × People) + (Ra × Area). These requirements ensure adequate dilution of CO₂, body odors, VOCs from materials, and other indoor pollutants.

ASHRAE 62.1 Ventilation Components

  • People Component (Rp): CFM per person to dilute occupant-generated pollutants (CO₂, odors, bioeffluents)
  • Area Component (Ra): CFM per square foot to dilute building-generated pollutants (VOCs from materials, furniture, finishes)
  • Total Ventilation: Vot = (Rp × People) + (Ra × Area)
  • Zone Air Distribution Effectiveness (Ez): Typically 1.0 for well-mixed systems
  • Multi-zone systems: Additional calculations required for system efficiency and diversity

How to Use This Calculator

  1. Select space type from predefined ASHRAE categories or choose Custom
  2. Enter floor area in square feet or square meters
  3. Choose occupancy input method: occupant count or occupancy density
  4. For occupant count: Enter number of people in the space
  5. For density: Enter people per 1000 ft² (or per 100 m²) - calculator estimates occupants
  6. For custom spaces: Enter Rp (CFM/person) and Ra (CFM/ft²) values
  7. Click Calculate to see total ventilation CFM and breakdown by component

Ventilation Calculation Formulas

1. Total Outdoor Air Required (ASHRAE 62.1)

Vot = Rp × Pz + Ra × Az

Where: Vot = outdoor air (CFM), Rp = outdoor air per person (CFM/person), Pz = zone population (people), Ra = outdoor air per area (CFM/ft²), Az = zone area (ft²)

2. Occupancy from Density

Occupants = (Floor Area × Density) / 1000 (for ft²) or / 100 (for m²)

3. Unit Conversions

  • 1 CFM = 0.4719 L/s
  • 1 ft² = 0.0929 m²
  • 1 CFM/ft² = 5.08 L/s/m²

ASHRAE 62.1 Standard Ventilation Rates

  • Office Space: Rp = 5 CFM/person, Ra = 0.06 CFM/ft² (typical density: 5 people/1000 ft²)
  • Classroom: Rp = 10 CFM/person, Ra = 0.12 CFM/ft² (density: 35 people/1000 ft²)
  • Conference Room: Rp = 5 CFM/person, Ra = 0.06 CFM/ft² (density: 50 people/1000 ft²)
  • Retail: Rp = 7.5 CFM/person, Ra = 0.12 CFM/ft² (density: 15 people/1000 ft²)
  • Restaurant: Rp = 7.5 CFM/person, Ra = 0.18 CFM/ft² (density: 70 people/1000 ft²)
  • Gym: Rp = 20 CFM/person, Ra = 0.06 CFM/ft² (density: 40 people/1000 ft²)
  • Library: Rp = 5 CFM/person, Ra = 0.12 CFM/ft² (density: 10 people/1000 ft²)
  • Hotel Bedroom: Rp = 5 CFM/person, Ra = 0.06 CFM/ft² (density: 10 people/1000 ft²)
  • Hospital Patient: Rp = 25 CFM/person, Ra = 0.06 CFM/ft² (density: 10 people/1000 ft²)

Common Applications

  • HVAC Design: Size outdoor air dampers and economizer systems
  • Energy Modeling: Calculate ventilation load for heating/cooling energy analysis
  • Code Compliance: Verify designs meet ASHRAE 62.1, IMC, local building codes
  • Indoor Air Quality: Ensure adequate fresh air for occupant health and comfort
  • Retrofit Analysis: Determine if existing systems provide adequate outdoor air
  • Demand Control Ventilation: Size CO₂ sensors and modulating dampers for DCV systems

Design Considerations

  • Default occupancy density vs actual: Use actual expected occupancy if known
  • Zone vs system efficiency: Multi-zone systems require additional calculations (Ez, Ev)
  • Altitude correction: High altitude locations need increased volumetric flow
  • Ventilation effectiveness: Displacement ventilation may allow reduced rates (Ez >1.0)
  • Residential vs commercial: ASHRAE 62.2 applies to residences, 62.1 to commercial
  • Ductwork leakage: Account for 10-25% outdoor air loss in duct systems

Ventilation Design Tips

  • ASHRAE 62.1 rates are minimums - consider increasing for improved IAQ
  • Higher occupancy spaces (conference rooms, classrooms) need higher Rp rates
  • Spaces with materials/finishes that off-gas VOCs need higher Ra rates
  • Don't forget area component - it can dominate in low-density spaces
  • Verify actual outdoor air delivery with pitot tube or airflow station measurements
  • Use demand control ventilation (DCV) in variable-occupancy spaces to save energy
  • Consider heat recovery (ERV/HRV) to reduce energy penalty of ventilation
  • Ensure adequate outdoor air intake location - away from exhaust, parking, loading docks

Energy Impact of Ventilation

  • Outdoor air is the largest energy load in many climates - must be heated/cooled to room temperature
  • In extreme climates, ventilation can account for 20-40% of total HVAC energy
  • Energy Recovery Ventilation (ERV) can reduce ventilation energy by 50-80%
  • Demand Control Ventilation (DCV) reduces outdoor air when spaces are unoccupied
  • Economizer mode uses outdoor air for free cooling when conditions permit

Common Mistakes

  • Using only Rp (people component) and ignoring Ra (area component)
  • Confusing total supply air with outdoor air - only outdoor air counts for ASHRAE 62.1
  • Using residential standard (62.2) for commercial buildings or vice versa
  • Not accounting for zone air distribution effectiveness (Ez)
  • Ignoring multi-zone system efficiency calculations for complex systems
  • Using default occupancy density when actual occupancy is known and different
  • Forgetting to verify outdoor air damper position and actual delivered airflow