Air Changes Per Hour Calculator
Free ACH calculator to determine air changes per hour based on room volume and airflow rate. Essential for HVAC design, ventilation, and indoor air quality.
What is Air Changes Per Hour (ACH)?
Air Changes Per Hour (ACH) is a measure of how many times the total volume of air in a defined space (room, building, zone) is completely replaced in one hour. For example, if a room has 4 ACH, the entire air volume is replaced 4 times every hour. ACH is critical for HVAC design, infection control in healthcare, manufacturing cleanrooms, odor control in kitchens/bathrooms, and general indoor air quality. Higher ACH rates improve air quality and dilute contaminants but increase energy consumption for heating/cooling fresh outdoor air.
Why ACH Matters
- Indoor Air Quality: Higher ACH dilutes pollutants, CO₂, VOCs, and odors
- Infection Control: Hospitals use high ACH (12-15+) to reduce airborne pathogens
- Moisture Control: Bathrooms/kitchens need high ACH to remove humidity
- Comfort: Adequate ACH prevents stuffy, stale air conditions
- Code Compliance: Building codes mandate minimum ACH for different spaces
- Energy Impact: Higher ACH increases HVAC energy costs significantly
How to Use This Calculator
- Select calculation mode: Calculate ACH or calculate required airflow
- Choose dimension unit: feet or meters
- Enter room dimensions (length, width, height) or direct volume
- For ACH calculation: Enter airflow rate in CFM, m³/h, or L/s
- For airflow calculation: Enter target ACH value
- Optionally select room type to see recommended ACH ranges
- Click Calculate to see results and compliance recommendations
ACH Calculation Formulas
1. Air Changes Per Hour (from CFM)
ACH = (CFM × 60) / Room Volume (ft³)
ACH = Airflow (m³/h) / Room Volume (m³)
2. Required Airflow (from ACH)
CFM = (ACH × Room Volume (ft³)) / 60
Airflow (m³/h) = ACH × Room Volume (m³)
3. Room Volume
Volume (ft³) = Length × Width × Height
ACH Standards by Room Type
- Residential Living Areas: 0.35-1 ACH (ASHRAE 62.2)
- Bedrooms: 2-4 ACH (sufficient for sleeping comfort)
- Kitchens: 7-15 ACH (remove cooking odors, heat, moisture)
- Bathrooms: 6-10 ACH (moisture and odor removal)
- Offices: 4-6 ACH (ASHRAE 62.1 commercial standard)
- Classrooms: 4-6 ACH (CDC/ASHRAE recommendations)
- Hospital General Rooms: 6-12 ACH (infection control)
- Hospital Isolation Rooms: 12-15+ ACH (airborne infection isolation)
- Laboratories: 6-20 ACH (depends on chemical use and fume hoods)
- Cleanrooms: 60-600+ ACH (ISO cleanroom classifications)
Common HVAC Applications
- Ventilation Design: Size exhaust fans and supply air systems
- Infection Control: Healthcare facilities, isolation rooms, operating rooms
- Indoor Air Quality: Ensure adequate fresh air for occupants
- Odor Control: Kitchens, bathrooms, pet areas, smoking rooms
- Moisture Control: Prevent mold growth, condensation issues
- HVAC Sizing: Determine required fan capacity and ductwork sizing
Factors Affecting ACH Requirements
- Occupancy Density: More people require higher ACH for CO₂ dilution
- Activities: Cooking, exercising, manufacturing increase ACH needs
- Pollutant Sources: Chemicals, smoke, VOCs require higher air changes
- Building Tightness: Newer tight buildings need mechanical ventilation
- Climate: Hot/humid climates may limit outdoor air to save energy
- Building Codes: Minimum ACH mandated by ASHRAE, IMC, local codes
ACH Design Tips
- Don't confuse ACH with outdoor air changes - total ACH includes recirculated air
- ASHRAE 62.1/62.2 specify minimum outdoor air, not total ACH
- Higher ACH improves air quality but significantly increases energy costs
- Use heat recovery ventilators (HRV/ERV) to reduce energy penalty of high ACH
- Ensure proper air distribution - dead zones won't benefit from high ACH
- Consider demand-controlled ventilation (DCV) with CO₂ sensors to vary ACH
- Pressurization matters: isolation rooms use negative pressure, cleanrooms positive
- Verify ACH with actual airflow measurements, not just design calculations
Energy & Cost Considerations
- Each ACH increase requires heating/cooling outdoor air (major energy cost)
- In extreme climates, high ACH can double HVAC energy consumption
- Heat recovery ventilation (HRV/ERV) can recover 60-90% of energy from exhaust air
- Optimize ACH to minimum required by code to save energy
- Variable-speed fans with DCV can reduce average ACH during low-occupancy periods
Common ACH Calculation Mistakes
- Confusing ACH with outdoor air changes (ACH includes recirculated air)
- Using incorrect units: CFM must be converted to ft³/hr (multiply by 60)
- Ignoring duct leakage: actual delivered airflow may be 10-30% less than fan rating
- Not accounting for air distribution: poorly designed systems have dead zones
- Assuming natural infiltration provides adequate ACH in tight modern buildings
- Forgetting to include all exhaust fans (kitchen, bath) in total ACH calculation